Home > Product > Indoor high voltage load switch > FKN12A- 12D Series air- blast load break switch

FKN12A- 12D Series air- blast load break switch

Intro:FKN12A- 12D Series air- blast load break switch and FKRN12A- 12D series air- blast load break switch-fuse combination apparatus are new series switchgear applies to three- phase electric distribution system of rated 12KV, acting as protecting and control apparatus for transformers, cable and overhead wiring. These series are especially applicable in rural, urban terminal substation and prefabricated substations, as well as ring network power supply.
Product Description

Description
      FKN12A-  12D Series air- blast load break switch and FKRN12A- 12D series air- blast load  break switch-fuse combination apparatus are new series switchgear applies  to three- phase electric distribution system of rated 12KV, acting as  protecting and control apparatus for transformers, cable and  overhead wiring. These series are especially applicable in rural, urban  terminal substation and prefabricated substations, as well as ring network  power supply.
      FKN12A-  12D series Load Break Switch can break and make load current and  over-current.  FKRN12A- 12D series air- -blast Load Break Switch can  break and make over-current, load current and short-circuit current (limited  current fuse).

Environment  condition
 - Ambient temperature: -45℃~+40℃
 - Altitude: ≤3000m
 - Relative humidity: monthly average ≤90%; daily  average: ≤95%
 - Wind pressure: ≤700Pa (equals to wind speed 34m/s)
 - Air contamination degree: IV degree

- No corrosive or flammable gas

Technical  Data

 DescriptionUnitFKN21-12D/T630-20FKRN21-12D/T125-31.5
Rated voltagekV12
Rated frequencyHz50
Rated currentA630125
Rated insulation
     level
1min power frequency with stand voltage
     (Phase to earth, phase to phase, between gaps)
kV4248
Rated lightning impulse withstand voltage
     (Phase to earth, phase to phase, between gaps)
kV7585
Rated peak withstanding currentkA50 
4S rated short-time withstanding currentkA /s20/
Earthing switch rated short-time withstanding current /
     Rated short-circuit duration time
kA/s20/4/
Rated breaking currentPower load breaking currentA630/
Close loop breaking currentA630/
Breaking cable charge currentA31.5/
Breaking no-load transformer capacitykVA12501250
Rated short-circuit breaking currentkA/31.5
Breaking transfer currentA/3150
Fuse type /SDLAJ-12,SFLAJ-12
Shocking input energyJ/3-5
Rated short-circuit making currentkA5080(expected)
Earthing switch rated withstand current(peak)kA5050
Earthing switch 4S rated short-time withstand currentkA2020
Auxiliary circuit rated voltageV220:110220:110
Mechanical life(grade M2)times20000

Outline & Mounting Dimensions 

111.jpg

112.jpg

PDF Material