Description
GN30-12(D) series Indoor high voltage disconnecting switches is a new type of touch rotating knife isolator , which special designed for XGN2-12 HV switchgear, with rated voltage 12kV and three phase AC 50Hz indoor device. It’s mainly used for making and breaking circuit under with voltage and no load.
Its main structure in three-phase chassis of the upper and lower two plane, fixed two set of insulator and contact, by rotating contactor, so as to realize switching on & off.
Environment condition
- Ambient temperature: max. +40°C min. -25°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Relative humidity: daily average ≤95%, monthly average ≤90%
- Earthquake intensity: ≤8 degree
- No corrosive, explosive or flammable gas ,no violent vibration
Technical Data
Model | GN30-12/ 400-12.5 | GN30-12/ 630-20 | GN30-12/ 1000-31.5 | GN30-12/ 1250-31.5 | GN30-12/ (1600-3150)-40 | |
GN30-12D/ 400-12.5 | GN30-12D/ 630-20 | GN30-12D/ 1000-31.5 | GN30-12D/ 1250-31.5 | GN30-12D/ (1600-3150)-40 | ||
Rated voltage (kV) | 12 | |||||
Rated current (A) | 400 | 630 | 1000 | 1250 | 1600-3150 | |
Rated short-time withstand current (kA) | 12.5 | 20 | 31.5 | 40 | ||
Rated short-circuit duration (s) | 4 | |||||
Rated peak withstand current (kA) | 31.5 | 50 | 80 | 100 | ||
Rated insulating level | 1min. PF withstand voltage (kV) | phase to phase/ to earth: 42, across open contacts: 49 | ||||
Lightning impulse withstand voltage (kV) | phase to phase/ to earth: 75, across open contacts: 85 |
Outline & Mounting Dimensions
GN30-12 | GN30-12D | |||||||||||||
400A, 630A | 1000A | 1250A | 400A, 630A | 1000A | 1250A | |||||||||
A | C | A | C | A | C | A | B | C | A | B | C | A | B | C |
~560 | ~315 | ~580 | ~332 | ~580 | ~295 | ~550 | ~610 | ~240 | ~575 | ~615 | ~245 | ~580 | ~600 | ~295 |