Intro:GW4 series Outdoor High Voltage disconnectors are 3 phase AC 50Hz high voltage switchgears. They are used in no-load condition to switch off the electric circuit and isolate electrical equipment, such as high voltage bus, circuit breaker etc, and high voltage line up to 252kV power system. The disconnecting switch can be divided into: No grounding, Single grounding and Double Grounding, and mechanical interlock is set between the main blade and earthing switch.
Product Description

Description

      GW4  series Outdoor High  Voltage disconnectors are 3 phase AC 50Hz high voltage switchgears. They are  used in no-load condition to switch off the electric circuit and isolate electrical equipment, such as high voltage bus, circuit breaker etc, and high voltage line up to 252kV power system. The disconnecting switch can be divided  into: No grounding, Single grounding and Double Grounding, and mechanical  interlock is set between the main blade and earthing switch.
      This product is double pole structure,  mainly consisting of frame, porcelains and conductive parts. Two porcelain  poles of each phase are mounted respectively on bearing holders of both ends of  the frame, and connected by cross links for horizontal rotation. Each of the conductive  blade is divided into two parts fixed on the two supporting porcelains, and the  contact part is right in the middle. It has pollution- proof type and plateau  type.

Environment  condition
 - Ambient temperature: max +40°C min -35°C
 - Altitude: ≤3000m
 - Wind pressure: ≤700Pa (equals to wind speed 34m/s)
 - Air contamination degree: IV degree

- Earthquake intensity: ≤8 degree
 - No corrosive or flammable gas

Technical  Data

1Rated Voltage (kV)40.5126252
21min power frequency withstand voltage
 (Effective value) kV
To Ground95230460
Between Fracture115245460+145
3Lightning Impulse withstand voltage
 (Peak value) kV
To Ground1855501050
Between Fracture2156301050+200
4Mechanical life (Times)2000
5Rated Current (A)400630100012501600200031504000
6Rated short time withstand Current (kA)202031.531.540405050
7Rated withstand current (Peak value) kA40508080100100125125
8Rated connect machine load (N)Horizontal vertical75010001000
Horizontal transverse500750750
Vertical force75010001000
9Creepage distance (mm)1013-22561813-22503150-3906
10Manual operating mechanismNo groundingCS11(F)
Single groundingCS8-6D(F)
Double groundingMain knife CS14G(F); Earth knife CS11(F)
Control loop voltage (V)AC220, DC110, DC220
11Motor operating mechanismModelCJ6
Motor voltage (V)AC220, DC380, DC220
Control loop voltage (V)AC220, DC380, DC220
Switching time (s)6±1

Outline & Mounting Dimensions 

图片2.png图片3.png

1.Base                  2. post insulator        3. Terminal     

4. Static  conducting tube   5. Waterproof cover    6. Dynamic conducting tube