Home > Product > Outdoor high voltage vacuum circuit breaker > FZW28-12F outdoor Boundary Vacuum Circuit Breaker

FZW28-12F outdoor Boundary Vacuum Circuit Breaker

Intro:FZW28-12F outdoor Boundary Vacuum Circuit Breaker, or called Boundary Load Break Switch, is applied to rated voltage 12kV, AC 50HZ outdoor distribution equipment , use for opening .closing load current and closing short circuit current . Applicable to substations and industrial and mining enterprises and city, rural network for protection and control purposes, and city, rural network automatic distribution net and frequent operation place .
Product Description

Description

      FZW28-12F outdoor Boundary Vacuum Circuit Breaker, or called  Boundary Load Break Switch, is applied to rated voltage 12kV, AC 50HZ outdoor  distribution equipment , use for opening .closing load current and closing  short circuit current . Applicable to substations and industrial and mining  enterprises and city, rural network for protection and control purposes, and  city, rural network automatic distribution net and frequent operation place .
      This  product is applicable for operation of control switch of overhead line  distribution systems, there are several types, VPS-12-type boundaries vacuum  load switch with no oil, institutional simple. Reliable, no maintenance and  other advantages, has been widely used. The product with the FDR-based fault  detector or RTU remote terminal unit equipment combine to form a very simple  structure, distribution automation system that allows the automatic overhead  lines fault location and fault segment of the automatic quarantine. In order to  update our existing distribution switchgear, so free of oil and automation  features of the distribution equipment for the transformation.

Environmental conditions
 1. Altitude: not higher than 2000m.
 2. Air temperature: -40℃  to +85℃
 3. Relative humidity: monthly average ≤90%, daily average: ≤95%
 4. Earthquake intensity: ≤ 8 degree
 5. Pollution Class: 3 degree
 6.Icing thickness:10mm
 7.Wind pressure: no more than 700Pa( equal  to wind speed 34m/s)

Technical Data

Rated voltageKV12
Rated currentA630
Rated frequencyHZ50
Rated short-time withstand current (4s)KA20
Rated short-circuit closing current (peak)KA50
Operation voltageVAC220 (80%-110%)
Power frequency withstand voltage(1min)To earthKV50 (GB.42)
Phase to phase50 (GB.42)
Fracture50 (GB.48)
Lightning impulse withstand voltageTo earthKV95 (GB.75)
Phase to phase95 (GB.75)
Fracture110 (GB.84)
Insulation resistanceTo earth 2000
Phase to phase2000
Fracture2000
Main loop resistance per phaseμΩ≤500
Working life under rated currentTimes10000
WeightKG185
Three phase contact closing and opening non-synchronismms≤2
Contact closing bounce timems≤5
Closing timems120-180
Opening timems500-900
Contact travelmm8-9
Contact over-travelmm2.5-4
Isolating gap open distancemm25-30
Isolation gap over line distancemm6-13
SF6 Leakage per year <1%
SF6 Gas moisture contentPPm<2
Standard IEC265-1

Outline & Mounting Dimensions

图片3.jpg

PDF Material