Home > Product > Outdoor high voltage vacuum circuit breaker > ZW43A-12F outdoor vacuum circuit breaker

ZW43A-12F outdoor vacuum circuit breaker

Intro:ZW43A-12F outdoor vacuum circuit breaker is used to make and break load current, overload current and short-circuit cur rent in 12kV, AC 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially for occasions with frequent operation and automatic power distribution network.
Product Description

Description 

      ZW43A-12F outdoor vacuum circuit breaker is used to make and  break load current, overload current and short-circuit cur rent in 12kV, AC 50/60Hz  power system. It is applicable for substations, industry and mining, urban and  rural electricity power networks, especially for occasions with frequent  operation and automatic power distribution network.
      It accords with the standard of IEC622 71-100 & GB1984:  AC high voltage circuit breaker, IEC60694 & GB/T11022: HV General technical  requirement of switch and control apparatus.

Technical Data

Rated voltagekV12
Rated insulation level1 min PF withstand voltageDry42/48
Wet34
Lightening impulse withstand voltage(peak)75/85
Rated currentA630
Rated short-circuit breaking currentkA20
Rated operating sequence  0-0.3s-co-180s-co
Opening times of rated short-circuit breaking currenttimes30
Rated short-circuit closing currentkA50
Rated peak withstand current
Rated short-time withstand current20
The duration of rated short circuits4
opening time0.040~0.060
closing time0.070~0.120
Mechanism lifeTimes10000
Rated closing operation voltageVAC/DC220,110
Rated opening operation voltageAC/DC220,110
Over current tripperCurrent setting multiples0.2~2.5
setting current tolerance±10%
delay setting value0-0.5
latency tolerance±10%
Instantaneous over-current protectioncurrent setting multiples2.5-10
setting current tolerance±10%
delay setting value0-0.5
latency tolerance±10%
AC input current charging control unitRating valueA5
Fluctuation rangeA0.5~8

Basic components:
 1. Current transformer protection poles 2 pcs
 2. Spring mechanism AC220V

Optional  components:
 1. Current transformer, metering and protection poles 2pcs each 75/5 or  higher
 2. Outside voltage transformer 2pcs (for control power supply and  metering)
 3. Motor spring mechanism AC/DC 220V/110V/48V/24V
 4. Reclosing controller and series FTU and RTU
 5. Disconnecting blade

Outline & Mounting Dimensions 

111.jpg

PDF Material