VS1 (ZN63A) -12 series

Intro:VS1 (ZN63A) -12 series indoor high voltage vacuum circuit breaker is three phase AC 50Hz indoor high voltage switchgear with rated voltage 12kV, divided into handcart type and stationary type. This VCB is widely used to power stations, substations, and industrial and mining enterprises to control or protection power transmission and distribution systems, specially for the important high altitude breaking load and frequent operation place and reliable interlock function.
VS1 (ZN63A)  -12 series
Product Description

Description
       VS1 (ZN63A)  -12 series indoor high voltage vacuum circuit breaker is three phase  AC 50Hz indoor high voltage switchgear with rated voltage 12kV, divided into  handcart type and stationary type. This VCB is widely used to power stations,  substations, and industrial and mining enterprises to control or protection power  transmission and distribution systems, specially for the important high  altitude breaking load and frequent operation place and reliable  interlock function.
 The operating  mechanism is for the spring energy storage type, can use AC and DC energy  storage operations. The circuit breaker can be used for extremely frequent  operation place, equipped with KYN28A-12 handcart type switch cabinet, and the  fixed type VCB can also be used for XGN series switch cabinets. It conforms to National  Standard GB1984-2003, and the related IEC standards.
       The circuit breaker is  designed as a front-rear split charging structure, which both can  be used as a fixed installation unit, and also be equipped with the chassis as  used in the mounted, handcart unit.

Environment  Condition:
 - Ambient temperature:-15℃~+40℃
 - Altitude: ≤1000m
 - Daily average relative humidity: ≤95%
 - Monthly average relative humidity: ≤90%
 - Earthquake intensity: ≤8  degree 
 - No fire, explosion, severe vibration, chemical  corrosion and serious pollution

Technical  Data

1Rated voltagekV12
2Max. working voltagekV12
3Rated CurrentA630, 12501600,2000
2500, 3150
2000, 2500
3150, 4000
4Rated short-circuit breaking currentkA20/2531.5040
5Rated short-circuit closing current (peak)kA50/6380100
6Rated peak withstand currentkA50/6380100
74s rated short-circuit withstand currentkA20/2531.5040
8Nos. of rated short-circuit breaking currentTimes50 (30 above 40kA)
9Rated operating sequence 0-0.3s-CO-180s-CO/
     0-180s-CO-180s-CO(Above 40KA)
10Rated lightning impulse withstand voltagekV75(Switch gap:85)
111min power frequency withstand voltagekV42 (Switch gap:48)
12Mechanical lifeTimes10000
13Contact open distancemm11±1
14Contact Over-travel (Length of spring compression)mm3.5±0.5
15Rated switch-on/off operating voltageVAC110/220,DC110/220
16Tripping timeMax. operating voltages≤0.05
Min. operating voltage≤0.08
17Closing times0.1
18Motor rated powerW70 (above 40kA: 100W)
19Average closing speedm/s0.5-0.8
20Average opening speedm/s0.9-1.2
21Contact closing bounce timems≤2
22Three phase contact closing opening asynchronyms≤2
23The main circuit resistance each phaseμΩ630A≤50, 1250A≤50, 1600A≤40
24Allowed consumpted thickness of contactsmm3