Home > Product > Indoor high voltage vacuum circuit breaker > VS1 (ZN63A) -12C series

VS1 (ZN63A) -12C series

Intro:VS1 (ZN63A) -12C series side mounted type indoor high voltage vacuum circuit breaker, is three-phase AC 50HZ indoor high voltage switchgear with rated voltage 12kV, used as protection and control electrical equipment. This VCB is specially used for the locations of frequently operation based on the rated current, or multiple breaking short circuit current.
VS1 (ZN63A)  -12C series
Product Description

Description
       VS1 (ZN63A)  -12C series side mounted type indoor high voltage vacuum circuit breaker, is  three-phase AC 50HZ indoor high voltage switchgear with rated voltage 12kV, used  as protection and control electrical equipment. This VCB is specially used for  the locations of frequently operation based on the rated current, or multiple  breaking short circuit current.
        The side mounted circuit  breaker is designed as a fixed type mount, and mainly  used in fixed type switchgear. It can be used separately, also be used for Ring  Main Unit, substation and non-standard power supply system.

Environment  Condition:
 - Ambient temperature:-15℃~+40℃
 - Altitude: ≤1000m
 - Daily average relative humidity: ≤95%
 - Monthly average relative humidity: ≤90%
 - Earthquake intensity: ≤8  degree 
 - No fire, explosion, severe vibration, chemical  corrosion and serious pollution

Technical  Data

1Rated voltagekV12
2Max. working voltagekV12
3Rated CurrentA630, 12501600,2000
2500, 3150
2000, 2500
3150, 4000
4Rated short-circuit breaking currentkA20/2531.5040
5Rated short-circuit closing current (peak)kA50/6380100
6Rated peak withstand currentkA50/6380100
74s rated short-circuit withstand currentkA20/2531.5040
8Nos. of rated short-circuit breaking currentTimes50 (30 above 40kA)
9Rated operating sequence 0-0.3s-CO-180s-CO/
0-180s-CO-180s-CO(Above 40KA)
10Rated lightning impulse withstand voltagekV75(Switch gap:85)
111min power frequency withstand voltagekV42 (Switch gap:48)
12Mechanical lifeTimes10000
13Contact open distancemm11±1
14Contact Over-travel (Length of spring compression)mm3.5±0.5
15Rated switch-on/off operating voltageVAC110/220,DC110/220
16Tripping timeMax. operating voltages≤0.05
Min. operating voltage≤0.08
17Closing times0.1
18Motor rated powerW70 (above 40kA: 100W)
19Average closing speedm/s0.5-0.8
20Average opening speedm/s0.9-1.2
21Contact closing bounce timems≤2
22Three phase contact closing opening asynchronyms≤2
23The main circuit resistance each phaseμΩ630A≤50, 1250A≤50, 1600A≤40
24Allowed consumpted thickness of contactsmm3

Outline & Mounting Dimensions

图片2.jpg

PDF Material