FLN36-12D(24D) sulfur hexafluoride Load Break Switch(LBS)

Intro:FLN36-12D(24D) sulfur hexafluoride Load Break Switch(LBS) is applied to indoor medium voltage switchgear of RMU, using SF6 gas as arc extinguishing and insulating medium.There are three working positions:open, closed, earth position in the switch, which is suitable for three phase AC 10Kv and 20Kv 50HZ power system, for cutting off and turning off load current and fault current.
Product Description

Description

      FLN36-12D(24D) sulfur hexafluoride Load Break Switch(LBS) is applied to indoor medium voltage switchgear  of RMU, using SF6 gas as arc extinguishing and insulating medium.There are three working positions:open, closed, earth position in the switch,  which is suitable for three phase AC 10Kv and 20Kv 50HZ power system, for  cutting off and turning off load current and fault current.

      It can be divided into two types: FLN36-12D ( K type single spring operating mechanism ),FLRN 36-12D (A type double spring operating mechanism). The second type could be equipped with fuse combination, having control and protecting function, which can be used for power supply and substation as a protecting and control device, especially suitable for ring main unit, cable distribution box and switching substation

     This LBS is  complied with the standards of IEC60265-1-1998, IEC60420

Environment  Condition:
 - Ambient temperature:-35℃~+40℃
 - Altitude: ≤2500m
 - Daily average relative humidity: ≤95%
 - Monthly average relative humidity: ≤90%
 - Earthquake intensity: ≤8  degree 
 - No fire, explosion, severe vibration, chemical  corrosion and serious pollution

Technical  Data

NO.DescriptionUnitParameter
FLN36-12D(24D)
1Rated voltagekV12(24)
2Rated CurrentkV630(630)
3Rated insulation level1min P.F. withstand voltage
 (Phase to phase/earth, between gaps)
kV42/48(65/79)
Lighting impulse withstand voltage
 (Phase to phase/earth, between gaps)
kV75/85(125/145)
4Rated short time withstand currentkA20(20)
5Rated duration of short circuits2(2)
6Rated short-circuit closing current (peak)kA50(50)
7Rated peak withstand currentkA 
8Rated breaking currentActive load breaking currentA630(630)
Closed loop breaking currentA630(630)
5% rated active load breaking currentA31.5(31.5)
Breaking cable charging currentA10(10)
Breaking non-load transformer capacitykVA1250(2000)
9Mechanical lifeTimes5000(5000)
10Rated pressure of SF6(20℃, gauge pressure)MPa0.04-0.05(0.04-0.05)

Outline & Mounting Dimensions