Home > Product > Indoor high voltage vacuum circuit breaker > VS1 (ZN63A) -24 series

VS1 (ZN63A) -24 series

Intro:VS1 (ZN63A) -24 series indoor high voltage vacuum circuit breaker is used for AC 24kV, 50Hz indoor high voltage switchgear, used as protection and control electrical equipment. This VCB is specially used for the locations of frequently operation based on the rated current, or multiple breaking short circuit current.
VS1 (ZN63A)  -24 series
Product Description

Description
       VS1 (ZN63A)  -24 series indoor high voltage vacuum circuit breaker is used for  AC 24kV, 50Hz indoor high voltage switchgear, used as protection and control  electrical equipment. This VCB is specially used for the locations of frequently operation based on the rated current, or multiple breaking short circuit  current.
       The VCB is  equipped with KYN28A-24 handcart type switch cabinet, and the fixed type VCB  can also be used for XGN series switch cabinets. It conforms to National Standard  GB1984-2003, and the related IEC standards.
       The circuit breaker is  designed as a front-rear split charging structure, which both can  be used as a fixed installation unit, and also be equipped with the chassis as  used in the mounted, handcart unit.

Environment  Condition:
 - Ambient temperature:-15℃~+40℃
 - Altitude: ≤1000m
 - Daily average relative humidity: ≤95%
 - Monthly average relative humidity: ≤90%
 - Earthquake intensity: ≤8  degree 
 - No fire, explosion, severe vibration, chemical corrosion  and serious pollution

Technical  Data

1Rated voltagekV24
2Rated frequencyHZ50
3Rated CurrentA630, 12501600,2000
 2500, 3150
2000, 2500
 3150, 4000
4Rated short circuit breaking currentkA20/2531.5040
5Rated short-time withstand voltagekV20/2531.5040
6Rated peak withstand currentkA50/6380100
7Rated short-circuit closing currentkA50/6380100
8Nos. of rated short-circuit breaking currentTimes50 (30 above 40kA)
9Rated operating sequence 0-0.3s-CO-180s-CO/
 0-180s-CO-180s-CO(Above 40KA)
10Rated lightning impulse withstand voltagekV125/145
 (between phases, to earth/switch gap)
111min power frequency withstand voltagekV65/79
 (between phases, to earth/switch gap)
12Mechanical lifeTimes20000
13Contact open distancemm16>±1
14Contact Over-travel (Length of spring compression)mm3.5±0.5
15Rated switch-on/off operating voltageVAC110/220,DC110/220
16Tripping timeMax. operating voltages≤0.05
Min. operating voltage≤0.08
17Closing times0.1
19Average closing speedm/s0.8±0.2-
20Average opening speedm/s1.5±0.2
21Contact closing bounce timems≤2 (40kA ≤3)
22Three phase contact closing opening asynchronyms≤2
23The main circuit resistance each phaseμΩ≤50(630A), ≤45(1250A),
 ≤35(1600-2000A), ≤25(2500A above)
24Allowed consumpted thickness of contactsmm3

Outline & Mounting Dimensions

1.jpg

PDF Material